Low Voltage Panel Technical Data
– Low voltage panel comprises incoming Air Circuit Breakers, horizontal and vertical busbars and outgoing Air Circuit Breakers / Molded Case Circuit Breakers. Our LV Panels are designed, manufactured and tested for short circuit current up to 85 kA.
Type | RFPB – P |
---|---|
Rated Insulation Voltage (Ui) | 690 V |
Rated Voltage (Un) | Up to 440 V 60Hz |
Rated Current (In) | Up to 3200 A |
Rated Short time withstand current (Icw) | 85 kA for 1 sec |
Degree of Protection (IP) | IP 54 (as required) |
Form of Separation | Up to Form 4B |
Application | Indoor / Outdoor |
Paint Color / Shade | RAL 7032 Powder Coating or (As required) |
Bus Duct /Cable Entry | Bottom / Top Entry (as required) |
Applicable Standard | IEC 61439-2 |